- 196 -
6. Description of Parameters
Function Code
Parameter Name
Setting Range
Default
F5-17
FMR output delay
0.0s to 3600.0s
0.0s
F5-18
Relay 1 output delay
0.0s to 3600.0s
0.0s
F5-19
Relay 2 output delay
0.0s to 3600.0s
0.0s
F5-20
DO1 output delay
0.0s to 3600.0s
0.0s
F5-21
DO2 output delay
0.0s to 3600.0s
0.0s
6
Value
Function
Description
33
Reverse running
Terminal set for this function becomes on when the AC drive runs in
reverse direction.
34
Zero current
Refer to descriptions of
and
.
35
IGBT temperature
reached
Terminal set for this function becomes on when heatsink
temperature of AC Drive IGBT (F7-07) reaches IGBT temperature
threshold (F8-47).
36
Output current
exceeding limit
Refer to descriptions of
and
.
37
Frequency lower
limit reached
(having output at
stop)
The terminal set for this function becomes on when the running
frequency reaches the frequency lower limit. When the drive stops,
the terminal remains on.
38
Alarm output
If a fault occurs on the AC drive and the AC drive continues to run,
terminal set for this function outputs an alarm signal.
39
Motor overheat
pending
Terminal set for this function becomes on when motor temperature
reaches value set in F9-58 (Motor overheat pending threshold). You
can view motor temperature by using U0-34.
40
Current running
time reached
Terminal set for this function becomes on when current running time
of the AC drive exceeds value set in F8-53.
41
Fault output
When a fault occurs on the AC drive (except undervoltage), terminal
set for this function becomes on.
These parameters set output delay of terminals FMR, relay1, relay2, DO1 and DO2 from state
change.
Function Code
Parameter Name
Setting Range
Default
F5-22
DI active mode
selection 1
0: Positive logic active
1: Negative logic active
00000
Units position: FMR active mode
Tens position: Relay1 active mode
Hundreds position: Relay2 active mode
Thousands position: DO1 active mode
Ten thousands position: DO2 active mode
- 196 -
This function parameter sets active mode of terminals FMR, relay1, relay2, DO1 and DO2.
●
0: Positive logic active
Digital output terminal becomes active when being connected with COM, and inactive when
being disconnected from COM.
●
1: Negative logic active
Digital output terminal becomes active when being disconnected from COM, and inactive
when being connected with COM.
Содержание GT600-4T132G
Страница 1: ...GT600 AC Drive...
Страница 5: ......
Страница 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Страница 87: ......
Страница 100: ...5 Quick Setup 98 5...
Страница 280: ...8 Peripherals and Options 278 8...
Страница 306: ...12 303 11...
Страница 362: ......