6.11.8 Current Detection
The drive provides two groups of current detection level and width.
If output current of the AC drive reaches the width, digital output terminals set for functions 28
and 29 become on.
Figure 6-68 Current detection
Output current
Current detection level
Current detection width
Current detection width
Current detection signal
DO or relay
OFF
ON
ON
ON
OFF
OFF
Function Code
Parameter Name
Setting Range
Default
F8-38
Detection level of current 1
0.0% to 300.0% (rated motor current)
100.0%
F8-39
Detection width of current 1
0.0% to 300.0% (rated motor current)
0.0%
F8-40
Detection level of current 2
0.0% to 300.0% (rated motor current)
100.0%
F8-41
Detection width of current 2
0.0% to 300.0% (rated motor current)
0.0%
6.11.9 Timing Function
Function Code
Parameter Name
Setting Range
Default
F8-42
Timing function
0: Disabled
1: Enabled
0
F8-43
Running time setting channel
0: Set by F8-44
1: AI1
2: AI2
3: AI3
(100% of analog input corresponds
to the value of F8-44)
0
F8-44
Running time
0.0 to 6500.0 min
0.0
These function parameters define the timing function of the drive. Once it is enabled, the AC
drive starts timing since start. When the set timing running time is reached, the AC drive stops
automatically and digital output terminal set for function 30 becomes on.
The AC drive starts timing from 0 again for each start. You can view remaining timing running
time in U0-20.
6
Содержание GT600-4T132G
Страница 1: ...GT600 AC Drive...
Страница 5: ......
Страница 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Страница 87: ......
Страница 100: ...5 Quick Setup 98 5...
Страница 280: ...8 Peripherals and Options 278 8...
Страница 306: ...12 303 11...
Страница 362: ......