10. Troubleshooting
- 293 -
■
Drive in V/F Control (F0-01 = 2)
It is applicable to application without an encoder for speed feedback. You need to set rated
motor voltage (F1-02) and rated motor frequency (F1-04) correctly.
Problem
Solutions
Motor oscillation
during running
Increase the setting of F3-11 (V/F oscillation suppression gain) by 10
gradually. The permissible maximum setting here is 100.
Overcurrent during
start
Decrease the setting of F3-01 (torque boost) by 0.5% gradually.
Very large current
during running
1. Set rated motor voltage (F1-02) and rated motor frequency (F1-04)
correctly.
2. Decrease the setting of F3-01 (torque boost) by 0.5% gradually.
Too loud motor noise
Increase the setting of F0-15 (carrier frequency) by 1.0 kHz gradually.
Note that increase in carrier frequency will result in an increase in the
leakage current of the motor.
Overvoltage detected
when heavy load is
suddenly removed or
during deceleration
1. Ensure that F3-23 (voltage limit selection) is set to 1 (enabled).
Increase the setting of F3-24/F3-25 (frequency gain/voltage gain for
voltage limit) by 10 gradually. The permissible maximum setting here is
100. The default value of F3-22 is 30.
2. Decrease the setting of F3-22 (voltage limit) by 10 V gradually. The
permissible minimum setting here is 700 V. The default value of F3-20
is 770 V.
Overcurrent detected
when heavy load is
suddenly added or
during acceleration
1. Increase the setting of F3-20 (current limit gain) by 10 gradually. The
permissible maximum setting here is 100. The default value of F3-22 is
20.
2. Decrease the setting of F3-18 (current limit level) by 10% gradually.
The permissible minimum setting here is 50%. The default value of
F3-18 is 150%.
10.3 Fault Display
When a fault occurs during running, the AC drive stops output immediately, the fault indicator
TUNE/TC
flashes, and contact of the fault relay acts. The operation panel displays the fault code such as
, as shown in the following figure.
RUN indicator
Tuning/Torque
control/Fault indicator
Fault dispay
Unit indicator
RUN
Stop/ Reset
11
RUN LOCAL / REMOT FED/ REV
TUNE / TC
Hz
A
V
RPM %
PRG
ENTER
QUICK
RUN
MF. K
STOP
RES
Содержание GT600-4T132G
Страница 1: ...GT600 AC Drive...
Страница 5: ......
Страница 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Страница 87: ......
Страница 100: ...5 Quick Setup 98 5...
Страница 280: ...8 Peripherals and Options 278 8...
Страница 306: ...12 303 11...
Страница 362: ......