8. Peripherals and Options
- 265 -
RS485 bus
485+
485-
120
Ω
terminal
resistor
CGND
485+ 485- CGND
485+ 485- CGND
Master
J3
MD38TX1
GT600
slave 1
120
Ω
terminal
resistor
GT600
slave N
MD38TX1
resistor
J3
485+ 485- CGND
Set J3 to
match terminal
8
●
PROFIBUS-DPbus topology
It is necessary to connect a matching terminal resistor to the end of PROFIBUS bus
and set DIP switch properly. The system PEs must be reliably grounded.
Length of communication cable between GT60DP2 and PROFIBUS-DP master varies
with different setting of baud rate of the master. Restrict communication cable lead
length strictly according to the Siemens DB9 standard. The following table describes
requirements on baud rate and communication cable lead length.
Baud Rate (Kbps)
Max. Length of Lead A (m)
Max. Length of Lead B (m)
9.6
1200
1200
19.2
1200
1200
187.5
600
600
500
200
200
1500
100
70
3000
100
Not supported
6000
100
12000
100