6. Description of Parameters
- 197 -
Function Code
Parameter Name
Setting Range
Default
A1-05
VDI active state setting
mode
0: Decided by state of VDOx
1: Decided by A1-06
00000
Units position: VDI1
Tens position: VDI2
Hundreds position: VDI3
Thousands position: VDI4
Ten thousands position: VDI5
A1-06
Selection of VDI active
state
0: Inactive
1: Active
00000
Units position: VDI1
Tens position: VDI2
Hundreds position: VDI3
Thousands position: VDI4
Ten thousands position: VDI5
6
6.9.3 Function of VDI Terminals
VDI terminals have the same functions as DI terminals do. They can be used for multi-functional
digital inputs.
Function Code
Parameter Name
Setting Range
Default
A1-00
VDI1 function selection
0 to 59
0
A1-01
VDI2 function selection
0 to 59
0
A1-02
VDI3 function selection
0 to 59
0
A1-03
VDI4 function selection
0 to 59
0
A1-04
VDI5 function selection
0 to 59
0
These function parameters set function to the five virtual DI terminals VDI1 to VD15, which have
the same digital input functions (0 to 59) as ten DI terminals do. For more details, see description
of
to
.
These function parameters determine active mode of VDI1 to VD15.
●
0: Decided by state of VDOx
To enable the AC drive to detect a fault and stop when input from AI1 input reaches limit,
perform the following settings:
– Set A1-00 to 44 to set VDI1 for function 44 “User-defined fault 1”.
– Set A1-05 to xxx0 to determine VDI1 active state by state of VDOx.
– Set A1-11 to 31 to set VDO1 for function 31 “AI1 input exceeding limit”.
When input from AI1 reaches limit, VDO1 becomes on. Then, VDI1 becomes on and the AC
drive receives user-defined fault.
Содержание GT600-4T132G
Страница 1: ...GT600 AC Drive...
Страница 5: ......
Страница 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Страница 87: ......
Страница 100: ...5 Quick Setup 98 5...
Страница 280: ...8 Peripherals and Options 278 8...
Страница 306: ...12 303 11...
Страница 362: ......