3. Electrical Installation
- 51 -
33
33
14-M12
R
U
35
S
V
35
T
W
135
60
62
161.5
300
236.5
85
50
2 13
48.5
31.5
3
60
36 65.2
42
3
13
8-M12
29
U
V
W
29
29
29
146
139
62
65
62
330
192.5
85
2 13
50
50
33
193.5
115
115
In
, the
side entry copper bar can be removed if necessary. Terminal dimensions of main circuit
terminals without side entry copper bar are shown below.
Figure 3-8 Terminal dimensions of GT600-4T200G-L/220G-L (without side entry copper bar,
without output reactor)
Table 3-7 Recommended cable dimensions and tightening torque of GT600-4T200G(-L)/220G(-L)
AC Drive Model
Rated Input
Current (A)
Power Input/
Output Cable
Crimp
Terminal
Model
Ground
Cable
Crimp
Terminal
Model
Tightening
Torque (N·m)
Screw
Spec.
GT600-4T200G(-L)
365
2 x (3 x 95) mm
2
4/0 AWG x 2P
100-12
95 mm
2
1 AWG
60-12
35.0
M12
GT600-4T220G(-L)
410
2 x (3 x 120) mm
2
300 kcmil x 2P
150-12
120 mm
2
1/0 AWG
60-12
35.0
M12
Figure 3-9 Terminal dimensions of GT600-4T250G/280G (without output reactor)