6. Description of Parameters
- 195 -
Value
Function
Description
10
Length reached
Terminal set for this function becomes on when detected actual
length exceeds value set in Fb-05.
11
PLC cycle
completed
Terminal set for this function outputs a pulse signal with width of 250
ms when simple PLC completes one cycle.
12
Accumulative
running time
reached
Terminal set for this function becomes on when accumulative
running time of the AC drive exceeds value set in F8-17.
13
Frequency limited
Terminal set for this function becomes on when frequency reference
exceeds frequency upper or lower limit, and output frequency of the
AC drive also reaches the upper or lower limit.
14
Torque limited
Terminal set for this function becomes on when the AC drive enters
stall protection because output torque reaches toque limit in speed
control.
15
Ready for RUN
Terminal set for this function becomes on when the AC drive is ready
to drive motor (Power applied to main circuit and control circuit is
normal, and no fault is detected).
16
AI1 > AI2
When AI1 input is greater than AI2 input, terminal set for this function
becomes on.
17
Frequency upper
limit reached
When running frequency reaches frequency upper limit, terminal set
for this function becomes on.
18
Frequency lower
limit reached (no
output at stop)
When running frequency reaches frequency lower limit, terminal set
for this function becomes on. When the AC drive is in stop status,
terminal set for this function becomes off.
19
Undervoltage
Terminal set for this function becomes on when undervoltage occurs
on AC drive.
20
Communication
setting
Whether terminal is active or inactive is determined by
communication address 0x2001.
21
Reserved
-
22
Reserved
-
23
Zero-speed
running 2 (having
output at stop)
When output frequency is 0 during drive running, terminal set for this
function becomes on. When the drive stops, terminal remains on.
24
Accumulative
power-on time
reached
Terminal set for this function becomes on when accumulative power-
on time of the AC drive (F7-13) exceeds value set in F8-16.
25
Frequency level
detection 2
Refer to descriptions of
and
.
26
Frequency 1
reached
Refer to descriptions of
and
.
27
Frequency 2
reached
Refer to descriptions of
and
.
28
Current 1 reached
Refer to descriptions of
and
.
29
Current 2 reached
Refer to descriptions of
and
.
30
Timing reached
On the condition that the timing function is enabled (F8-42 = 1),
terminal set for this function becomes on when current running time
of the AC drive reaches the set time.
31
AI1 input
exceeding limit
Terminal set for this function becomes on when AI1 input is larger
than value set in F8-46 (AI1 input voltage upper limit) or smaller than
value set in F8-45 (AI1 input voltage lower limit).
32
Load lost
Terminal set for this function becomes on when load gets lost.
6
Содержание GT600-4T132G
Страница 1: ...GT600 AC Drive...
Страница 5: ......
Страница 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Страница 87: ......
Страница 100: ...5 Quick Setup 98 5...
Страница 280: ...8 Peripherals and Options 278 8...
Страница 306: ...12 303 11...
Страница 362: ......