Table 89: Warning messages
Message
Description
WARNING – UPS – LINE LOW
BATTERY VOLTAGE
This auto reset warning is set when all of the following are true:
•
Control Voltage digital input is high (indicates line power is available)
•
Battery Voltage < Line Low Battery Voltage Threshold
It releases when Battery Voltage > Line Low Battery Voltage Thr 0.1 V.
WARNING – UPS – NOT
CHARGING
This auto reset warning is set when all of the following are true for 5 continuous seconds:
Control Voltage digital input is high (indicates line power is available)
•
UPS Line / Charging digital input is low (indicates UPS not reporting in charge mode)
It releases when any of the following are true:
•
Control Voltage digital input is low (indicates line power is lost)
•
UPS Line / Charging digital input is high (UPS is reporting in charge mode)
WARNING – VSD – INPUT
VOLTAGE IMBALANCE
Line voltage imbalance is calculated, for every drive communications cycle, as:
where V
ab
, V
bc
and V
ca
are line-to-line total rms voltages received from the drive, max is the
function which selects the largest of its arguments, and:
If Vimb% exceeds 5% continuously for 45 seconds, the warning is displayed. The 45 second
timer resets and the warning clears if three consecutive imbalance readings fall below the
5% threshold.
Routine shutdown messages
Table 90: Routine shutdown messages
Message
Description
LOCAL STOP
A local shutdown command has been received by pressing the Keypad Stop key.
REMOTE STOP
A shutdown command has been received from a remote device. Remote Stop commands
can be received in Digital Remote mode via I/O Board TB4-7/8 or in BAS (ISN) (Integrated
Systems Network) Remote mode via the SC-Equip Gateway serial communications. If the
chiller is running when this occurs, the chiller performs a soft shutdown.
93
YVAM Control Center
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...