Figure 49: Smart sensor system components location
Callout
Description
A
Smart sensor board mounted behind door rail
B
Smart sensors
Note:
Variable speed drive model HYP0490 shown, other models are similar.
OptiSpeed compressor drive and chiller operation (0490B
amp models)
When the chiller enters a start command, the OSCD is commanded to pre-charge. The pre-charge
contactor closes and slowly charges the DC Bus capacitors through the pre-charge resistors. This is
called the pre-charge period, which lasts for 12 seconds. When the 12-second time period expires,
the supply contactor closes and the pre-charge contactor opens. The supply and pre-charge
contactors remain in this state for the duration of the run cycle. The OSCD logic board provides the
commands for the supply and pre-charge contactors.
All models of HYP drives control the motor in the same manner for a normal stop command.
YVAM Control Center
120
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...