Evaporator screen
Figure 14: Evaporator screen
This screen displays a cutaway view of the chiller evaporator. All setpoints relating to the
evaporator side of the chiller are maintained on this screen. Animation of the evaporation process
indicates whether the chiller is presently in a Run condition. Animation of the liquid flow indicates
chilled liquid flow.
Table 15: Display only fields
Field/LED name
Description
Leaving Chilled Liquid Temperature Displays the temperature of the liquid as it leaves the evaporator.
Entering Chilled Liquid Temperature Displays the temperature of the liquid as it enters the evaporator.
Evaporator Small Temperature
Difference
Displays the difference between the Leaving Chilled Liquid temperature and the
Evaporator Refrigerant temperature. The Evaporator Refrigerant temperature is
represented by the Refrigerant Temperature sensor input if the sensor is enabled.
Otherwise it is represented by the Evaporator Saturation temperature.
Evaporator Pressure
Displays the present refrigerant pressure in the evaporator.
Leaving Chilled Liquid Temperature
Setpoints–Setpoint
Displays the present setpoint to which the chiller is operating, whether controlled
locally or remotely.
Leaving Chilled Liquid Temperature
Setpoints–Restart
Displays the Leaving Chilled Liquid Temperature at which the chiller restarts after it
shuts down on
LEAVING CHILLED LIQUID – LOW TEMPERATURE
cycling shutdown.
This temperature is set as an offset using the Leaving Chilled Liquid Temperature
Cycling Offset –Restart setpoint.
Leaving Chilled Liquid Temperature
Setpoints (Shutdown) – Effective
Offset
Displays the present value of the leaving chilled liquid temperature shutdown offset in
effect, limited by the chiller minimum temperature.
Leaving Chilled Liquid Temperature
Setpoints (Restart) – Offset
Displays the value set for leaving chilled liquid temperature restart offset.
Evaporator Saturation Temperature Displays the present saturation temperature in the evaporator, determined from the
evaporator pressure.
Chilled Liquid Flow Switch (Open/
Closed)
Displays whether the liquid flow switch input indicates flow is present in the
evaporator.
Chilled Liquid Pump
Displays the command presently sent by the control center to the Chilled Liquid Pump
run contacts: Run or Stop.
37
YVAM Control Center
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...