Table 35: Display only fields
Field/LED name
Description
Voltage Total Harmonic
Distortion - (L1, L2, L3)
Displays the Total Harmonic Distortion (THD) for each of the voltage lines as calculated by
the VSD.
Input Current Total Demand
Distortion - (L1, L2, L3)
Displays the Total Dynamic Distortion (TDD) for each of the supply current lines as calculated
by the variable speed drive.
Input Job Full Load Amps
Shows the job input full load amp limit within a range limited from 10% to 100% of the drive
nominal input current at nominal line voltage.
Table 36: Programmable
Button
Access
Description
Local Input Current Limit
Operator
Allows the user to specify the maximum allowed input current (as a
percentage of job FLA). When the input current reaches this value, the input
current override takes effect.
Pulldown Demand Limit
Operator
Allows the user to specify the current limit value (as a percentage of FLA)
to which the chiller will be limited during the specified pulldown limit time.
This value will override the input Current Limit value during this time period.
This function is used to provide energy savings following chiller start-up.
Pulldown demand limit is ignored in BAS (ISN) control source because the
BAS system is expected to use its algorithms to reset current limit as required
in that operating mode.
Pulldown Demand Time
Operator
Allows the user to set a period of time for which the pulldown demand limit
will be in effect after the chiller starts.
Table 37: Navigation
Button
Description
Home
Returns to the Home screen.
VSD Details
Navigates to the variable speed drive details screen.
Motor Details
Navigates to the Motor Details Screen.
Capacity Control
Navigates to the Capacity Control screen.
Power Panel
Navigates to the Power Panel screen.
YVAM Control Center
54
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...