WARNING
All appropriate electrical safety measures must be followed when testing these heaters because these
circuits will be energized.
CAUTION
The evaporator water loop must be filled before conducting the following tests to prevent damage to
the heaters for the evaporator related components.
Testing evaporator waterbox heaters WBH1 and WBH2
The evaporator waterbox heaters WBH1 and WBH2 are powered by the customer by the HTR DIST
enclosure.
1. Unplug the ambient temperature sensor to the OptiView by removing the J10 plug from the
microboard to energize the heater.
2. At the HTR DIST panel, use wires 131 and 131A to measure the current to the heaters. The
nominal current for each one is 3 A. However, it might read lower values based on the load at
the time of testing.
3. Return the J10 connector immediately after recording the current value. Record the value in
160.88-CL2
.
Testing evaporator shell heaters EVH1 and EVH2
The evaporator shell heaters EVH1 and EVH2 are powered by the auxiliary power panel enclosure.
1. Unplug the ambient temperature sensor to the OptiView by removing the J10 plug from the
microboard to energize heaters.
2. At the auxiliary power panel, use wires 325 and 325 A to measure the current to the heaters.
The nominal current for each one is 1 A. However, it may read lower values based on the load
at the time of testing.
3. Return the J10 connector immediately after recording the current value. Record the value in
160.88-CL2
.
Testing heat trace for drive coolant HT1 and HT2
The heat trace for variable speed drive coolant HT1 and HT2 is powered by the customer by the HTR
DIST enclosure.
1. Unplug the ambient temperature sensor to the OptiView by removing the J10 plug from the
microboard to energize the heater.
2. At the HTR DIST panel, use wires 131 and 131A to measure the current to the heaters. The
nominal current for each one is 2 A. However, it may read lower values based on the load at
the time of testing.
3. Return the J10 connector immediately after recording the current value. Record the value in
160.88-CL2
.
141
YVAM Control Center
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...