Figure 55: Drive internal heater
3. Record the value in
160.88-CL2
.
4. Return the temperature setting to 32°F when testing is complete.
Testing the OptiView control panel heater
1. Measure the current to the heater using wire 31A at 5BR on TB6 in the Optiview Panel. The
nominal current is 1.5 A. However, it might read lower values based on the load at the time of
testing.
2. Adjust the temperature high enough to energize the heater based on the ambient
temperature at commissioning.
3. When testing is complete, reset the setting to 32°F (0°C). See Figure 56 for the thermostat
locations in the chiller control panel. See Figure 57 for the control options on the thermostat.
Note that one of two thermostat options can be installed. Both images are included in Figure
57.
4. Record the value in
160.88-CL2
.
143
YVAM Control Center
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...