Conducting the gas pressure hold test
1. To monitor the system pressure over time, install a high-quality, high-resolution analog
pressure gauge on one of the shells. Use a pressure gauge that has a resolution of 2 psi
increments with a dial face at 3 in. in diameter or greater.
2. Before proceeding, make sure that the unit is at the initial evacuation level of 5 mmHg.
Important:
To prevent freezing of any moisture that might be in the system, do not go
below 5 mmHg. See
for more details.
3. With the system in a vacuum, slowly charge nitrogen vapor only into the system.
4. Slowly build up the system pressure with dry nitrogen to the design working pressure (DWP)
as found on the chiller vessel data plates.
5. Allow the pressure to remain in the chiller based on Figure 51. This chart provides the hold
times for pressure hold testing based on the vessel diameter and length.
What to do next:
•
For a unit with no loss of pressure, proceed to unit evacuation.
•
For units where a leak is suspected and there is any amount of drop in recorded pressure,
proceed to either of the following leak detection methods:
Conducting the soap visual gas
Conducting the optional trace gas leak test
.
125
YVAM Control Center
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...