Table 92: Safety shutdown messages
Message
Description
MOTOR –
HIGH WINDING
TEMPERATURE
This safety shutdown occurs when any of the enabled motor winding temperatures exceeded the
programmed High Winding Temperature Shutdown Threshold of 302˚F (150˚C) for 3 continuous
seconds. The chiller can be started after all winding temperatures decreased to at least 18˚F (10˚C)
below the shutdown threshold and the compressor is stopped. The safety shutdown will not act on
any individual winding temperature sensor that has been disabled with the Temperature Disable
setpoint on the Motor Details Screen.
MOTOR – HIGH
ROTOR TEMPERATURE
This safety shutdown occurs when the estimated rotor temperature exceeds 250.0˚F for 3 continuous
seconds. The fault is released and the chiller can be restarted when the estimated rotor temperature
is below 230˚F and the Clear Faults button is pressed on the OptiView panel.
MOTOR –
HIGH HOUSING
TEMPERATURE
This is set when Motor Housing Temperature is greater than or equal to 185°F (85°C). This fault is
released when Motor Housing Temperature is less than 158°F (70°C). The chiller can be started when
the condition is released and the Clear Faults button is pressed on the OptiView panel.
SALES ORDER
- INVALID
COMPRESSOR MODEL
This safety shutdown is set when the Compressor Model field entered on the
Setpoints
>
Setup
>
Sales Order
screen does not conform to the format expected. The format is
defined below and the data can be found on the compressor nameplate if it ever needs re-entry in
the control:
Motor
Motor
rev
SS/LS Imp. Dia.
SS/LS
rotation
SS/LS
Imp.
Dia.
SS/LS
flow
rev
HS Imp. Dia. HS rotation
HS
Imp.
rev
HS flow
rev
:code
1,2
3
-
4
5
6
7
8
9
- 10 11 12
13
14
15
:Position
The
Sales Order - Invalid Compressor Model
safety shutdown is set when any of the
following are true:
•
Motor is anything other than M2 or M6
•
Motor Rev is anything other than C
•
Character other than ‘-‘ between position 3 and 4
•
SS/LS Imp. Diam. is anything other than 164, 174, 186, 197, 205, 218, 233, 246, 275, 295, or 331
•
SS/LS Rotation is anything other than F
•
SS/LS Imp. Rev. is anything other than the character A
•
SS/LS Flow Rev. is anything other than the character C
•
Motor Model is invalid
•
Invalid impeller/motor combination
The following table shows all valid impeller and motor combinations for single stage:
Compressor
Motor
197FA
M1
M2
205FA
M1
M2
218FA
M1
M2
233FA
M2
M4
246FA
M2
M4
M6
275FA
M4
M6
295FA
M4
M6
331FA
M6
The following table shows all valid impeller and motor combinations for two stage:
Compressor
Motor
233FA / 205RA
M1
M2
275FA / 241RA
M2
M4
M6
331FA / 291RA
M4
M6
The fault is released when the values have been corrected. The chiller can be restarted after the Clear
Faults button is pressed.
YVAM Control Center
106
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...