AIR FLOW REQUIREMENTS
Calculate KW per square foot of duct area as:
(see step 12)
heater namplate KW
duct area (Sq.Ft.)
FIG. 1 - MINIMUM AIR VELOCITY REQUIRED FOR SAFE OPERATION
OPERATION & MAINTENANCE
All sources of supply must be discon-
nected before working on this equip-
ment
To operate this heater make sure all associated control
equipment is on, energize main supply disconnect and
set controlling thermostat above ambient temperature.
This heater is equipped with automatic and manual
reset temperature limiting controls. If it fails to operate,
make sure manual resets are operative by pushing reset
buttons.
The only routine maintenance required is to check all
electrical connections, including field and factory made
connections, for tightness at least once each year or
operating season. In addition, of course, any filters in
the airstream must be kept clean so that adequate airflow
is maintained.
100
2
200 300 400 500 600 700 800 900 1000 1100 1200
4
6
8
10
12
14
16
0
0
100
2
200 300 400 500 600 700 800 900 1000 1100 1200
4
6
8
10
12
14
16
18
22
24
26
28
30
32
20
0
0
KW
PER
SQ.
FT.
DUCT
AREA
MINIMUM AIR VELOCITY REQUIRED
(FEET PER MINUTE)
K
W
P
E
R
S
Q
. F
T.
D
U
C
T
A
R
E
A
MINIMUM AIR VELOCITY REQUIRED
(FEET PER MINUTE)
FINNED
TUBULAR
CONSTRUCTION
91
- 100°
Inlet
Air
81
-
90°
Inlet
Air
Be
lo
w
80
° I
nl
et
A
ir
OPEN COIL
CONSTRUCTION
3
jOHNSON CONTROLS
FORM 102.20-N1 (509)
Содержание YORK SOLUTION LD09624
Страница 4: ...johnson controls 4 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...johnson controls 10 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 16: ...johnson controls 16 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...johnson controls 1 8 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 106: ...johnson controls 2 76 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 133: ...3 27 johnson controls FORM 102 20 N1 1109 3 FIG 3 28 AIR handler start up checklist FORM 100 00 CL1 ...