5. Supply conductors for heaters rated less than 50
KW, must be sized at 125% of rated load. On heat
-
ers rated 50 KW and more, the supply conductors
may be sized at 100% of rated load, if indicated
on the wiring diagram. The line current for either
a single or three phase load is calculated as fol
-
lows:
Single Phase Line Current =
KW x 1000
Voltage
Three Phase Line Current =
KW x 1000
Voltage x 1.73
6. The following table shows the maximum current
for 75 °C copper wire with not more than 3 con
-
ductors in a raceway. It is based on the National
Electrical Code Table 310-16. The amperages
shown are for 125% and 100% wire sizing. If there
are more than 3 conductors in a raceway, derate
these amperages per Table 310-15(b)(2)(a).
AMPS
WIRE
SIZE
AWG/
MCM
AMPS
WIRE
SIZE
AWG/
MCM
AMPS
WIRE
SIZE
AWG/
MCM
125% 100%
125% 100%
125% 100%
12
14
80
100
3
184
230
4/0
16
12
92
115
2
204
255
250
24
10
104
130
1
228
285
300
40
8
120
150
0
248
310
350
52
65
6
140
175
2/0
268
335
400
68
85
4
160
200
3/0
304
380
500
7. When connecting heaters with more than one stage,
wire stage No. 1 so that it is the first stage on and
the last stage off.
8. The heater must be wired so that it cannot operate
unless air is flowing over it. This can be accom
-
plished by using a built-in airflow switch and a
remote interlock.
See the accompanying wiring
diagram for the method used with this heater and
provide appropriate interlock wiring as illustrated.
This diagram will be located inside of the electric
heater control panel.
9. If not supplied as part of this heater, install a
line disconnect switch or main circuit breaker in
accordance with the National Electrical Code.
Depending upon the heater’s location and acces
-
sibility, a built-in disconnect switch may meet this
requirement.
10. All electrical connections in the heater, including
both field and factory made connections, should be
checked for tightness before operating the heater.
In addition, after a short period of operation, all
connections should again be checked for tight
-
ness.
11. If heater is wired to a heating / cooling thermostat,
use a thermostat with isolating circuits to prevent
possible interconnection of Class 2 outputs.
12. If the heating elements are divided into several
sections with resistance wire between two or more
sections, maximum KW per sq. ft. should be cal
-
culated as follows:
Number of heated sections x
area of one heated section
Heater nameplate KW
jOHNSON CONTROLS
2
FORM 102.20-N1 (509)
Содержание YORK SOLUTION LD09624
Страница 4: ...johnson controls 4 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...johnson controls 10 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 16: ...johnson controls 16 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...johnson controls 1 8 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 106: ...johnson controls 2 76 FORM 102 20 N1 1109 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 133: ...3 27 johnson controls FORM 102 20 N1 1109 3 FIG 3 28 AIR handler start up checklist FORM 100 00 CL1 ...