SECTION 5 - JLG CONTROL SYSTEM
5-66
31215923
5.8
CALIBRATION PROCEDURES
Chassis Tilt Sensor - Non QuikLevel Equipped
Machine
1. Drive the machine onto a measured level surface
(±0.5° for both x and y axis) and ensure the platform
is stowed.
2. Using the Analyzer, go to MENU: CALIBRATION; TILT
SENSOR. Press Enter. LEVEL VEHICLE will display.
Press Enter again to calibrate.
3. Both axis’ raw angles need to be within
1.0°, other-
wise the machine is not level and the software will
prohibit calibration. Should this occur, check for the
following:
a.
Machine mounting and/or grade:
With a digital level, measure the chassis for lev-
elness.
b.
Tilt sensor mounting on machine:
Remove the tilt sensor from the chassis, but
keep the tilt sensor electrically connected.
Level one axis of the tilt sensor and observe
the raw reading (should be within ±1.0°). Do
the same for the other axis. If either axis is
greater than ±1.0°, replace the tilt sensor.
Some possible reasons that the tilt sensor will
not calibrate are:
A. The surface the machine is sitting on is off level
by a few degrees (flat doesn't imply level; park-
ing lots are often not level).
B. The tilt sensor has failed one or both of the
channels (X axis and Y axis).
c. Tilt sensor has moisture intrusion that has
shifted its output.
d. Water and/or corrosion in the box has cor-
rupted electrical connections or caused a tilt
sensor or ground control board failure observe
any cracks in the box).
For the following troubleshooting steps, a bubble level
(smaller is better) will be needed and the machine must
be on a level surface:
1. On the Analyzer, go to Diagnostics/System and read
the tilt angle. If either angle r20.0°, there is
an electrical/electronic failure (tilt sensor, control
board, electrical connections).
a. Disconnect the sensor and clean any corrosion
off of the tilt sensor and control board connec-
tions.
b. Reassemble and test. If fault persists, replace
tilt sensor.
2. If the Analyzer displays angles other than +20.0°,
attempt to calibrate. If machine will not calibrate,
note the reason displayed on Analyzer:
a. SENSOR FAILURE - tilt sensor communication
can not be established.
b. NOT LEVEL - tilt sensor has either developed an
offset or it is too unlevel as mounted on the
machine or the surface on which the machine
sits is not level.
Содержание ERT2669
Страница 2: ......
Страница 4: ...INTRODUCTION A 2 31215923 REVISON LOG Original Issue A January 08 2021...
Страница 12: ...viii 31215923 TABLE OF CONTENTS...
Страница 40: ...SECTION 1 SPECIFICATIONS 1 22 31215923...
Страница 58: ...SECTION 2 GENERAL 2 18 31215923...
Страница 187: ...SECTION 4 BASIC HYDRAULIC INFORMATION SCHEMATICS 31215923 4 11...
Страница 206: ...SECTION 4 BASIC HYDRAULIC INFORMATION SCHEMATICS 4 30 31215923...
Страница 221: ...SECTION 4 BASIC HYDRAULIC INFORMATION SCHEMATICS 31215923 4 45 Figure 4 33 Lift Cylinder MAF46290...
Страница 223: ...SECTION 4 BASIC HYDRAULIC INFORMATION SCHEMATICS 31215923 4 47 Figure 4 35 Leveling Jack Cylinder MAF46280...
Страница 225: ...SECTION 4 BASIC HYDRAULIC INFORMATION SCHEMATICS 31215923 4 49...
Страница 242: ...SECTION 4 BASIC HYDRAULIC INFORMATION SCHEMATICS 4 66 31215923...
Страница 307: ...SECTION 5 JLG CONTROL SYSTEM 31215923 5 65...
Страница 334: ...SECTION 6 LSS SETUP CALIBRATION SERVICE 6 12 31215923...
Страница 362: ...SECTION 7 GENERAL ELECTRICAL INFORMATION SCHEMATICS 7 28 31215923...
Страница 374: ...SECTION 7 GENERAL ELECTRICAL INFORMATION SCHEMATICS 7 40 31215923...
Страница 375: ......