19
UMG 96RM-M
c
Attention!
Voltages that exceed the permitted
ratedmains voltages must be connected
via voltage transformers.
c
Attention!
The UMG 96RM-M is not suitable for
the measurement of DC voltages.
c
Attention!
The voltage measurement inputs on
the UMG 96RM-M are dangerous
to touch!
When connecting the voltage to be measured,
the following must be observed:
Isolation device
• A suitable circuit breaker must be fitted to disconnect
and de-energise the UMG 96RM-M.
• The circuit breaker must be placed in the vicinity of
the UMG 96RM-M, be marked for the user and easily
accessible.
• The circuit breaker must be UL/IEC certified.
Overcurrent protection device
• An overcurrent protection device must be used for
line protection.
• For line protection, we recommend an overcurrent
protection device as per the technical specifications.
• The overcurrent protection device must be suitable
for the line cross section used.
• The overcurrent protection device must be UL/IEC
certified.
• A circuit breaker can be used as an isolating and line
protection device. The circuit breaker must be UL/IEC
certified.
• Measured voltages and measured currents must
derive from the same network.
Содержание UMG 96 RM-M
Страница 13: ...13 UMG 96RM M...
Страница 15: ...15 UMG 96RM M...
Страница 33: ...33 UMG 96RM M...
Страница 65: ...65 UMG 96RM M Work values within the software GridVis Control of the values 187E 6270 10 resolution 62700 Wh...
Страница 81: ...81 UMG 96RM M...
Страница 102: ...102 UMG 96RM M Dimensional drawings All dimensions in mm max 6 91 5 104 96 42 Rear view Side view...
Страница 103: ...103 UMG 96RM M Bottom view 97 91 5 Cutout dimensions 92 0 8 92 0 8...
Страница 111: ...111 UMG 96RM M...