32
UMG 96RM-M
Digital outputs
The UMG 96RM-M has 2 digital outputs. These outputs
are electrically isolated from the evaluation electronics
by optocouplers. The digital outputs have a common
reference.
• The digital outputs can switch DC and AC loads.
• The digital outputs are
not short circuit protected.
• Connected cables longer than 30 m must be shielded.
• An external auxiliary voltage is required.
• The digital outputs can be used as pulse outputs.
• The digital outputs can output results from
comparators.
Fig. Connection of digital/pulse
outputs
~
Abb. Anschluss von zwei Relais an die digitalen Aus-
gänge 14 und 15.
C
When using the digital outputs as a pulse
output, the auxiliary voltage (DC) must only
have a maximum residual ripple of 5%.
K1
K2
24 V
AC/DC
External
auxiliary voltage
UMG 96RM-M
Digital outputs 1-2
Digital outputs 1-2
14
Digital
output 1
15
Digital
output 2
13
~
~
AC/DC
AC/DC