UMG 96RM-M
Configuration
Applying the supply voltage
To configure the UMG 96RM-M, the supply voltage must
be connected.
The level of supply voltage for the UMG 96RM-M can
be found on the nameplate.
If no display appears, check the operating voltage
to determine whether it is within the rated voltage range.
Current and voltage transformers
A current transformer is set to 5/5 A in the factory.
The pre-programmed voltage transformer ratio only
needs to be changed if voltage transformers are
connected.
When connecting voltage transformers, the measure-
ment voltage on the UMG 96RM-M nameplate must be
observed!
c
Attention!
Supply voltages that do not correspond
to the nameplate information can lead
to device malfunction or destruction.
C
The adjustable value 0 for the primary
current transformer does not produce
any useful energy values and must not
be used.
m
Devices, which are programmed to au-
tomatic frequency detection, need ap-
proximately 20 seconds to detect grid
frequency. During this period, the mea-
sured values do not keep the confirmed
measuring accuracy.
C
Prior to commissioning potential produc-
tion dependant contents of the energy
counter and min/max values have to be
deleted.
Содержание UMG 96 RM-M
Страница 13: ...13 UMG 96RM M...
Страница 15: ...15 UMG 96RM M...
Страница 33: ...33 UMG 96RM M...
Страница 65: ...65 UMG 96RM M Work values within the software GridVis Control of the values 187E 6270 10 resolution 62700 Wh...
Страница 81: ...81 UMG 96RM M...
Страница 102: ...102 UMG 96RM M Dimensional drawings All dimensions in mm max 6 91 5 104 96 42 Rear view Side view...
Страница 103: ...103 UMG 96RM M Bottom view 97 91 5 Cutout dimensions 92 0 8 92 0 8...
Страница 111: ...111 UMG 96RM M...