87
UMG 96RM-M
Possibility of error
Cause
Help
Ind./cap. phase shift
The current circuit is assigned to the
wrong voltage circuit.
Check and correct the connection if
necessary.
Real power is too small or too large.
The programmed current transformer ratio
is incorrect.
Reading and programming the current
transformer ratio on the current
transformer
The current circuit is assigned to the
wrong voltage circuit.
Check and correct the connection if
necessary.
The programmed voltage transformer ratio
is incorrect.
Read and program the voltage transformer
ratio on the voltage transformer.
The active energy import/export is
inverted.
At least one current transformer
connection is inverted.
Check and correct the connection if
necessary.
A current circuit is assigned to the wrong
voltage circuit.
Check and correct the connection if
necessary.
An output is not reacting.
The output was incorrectly programmed.
Check the programming and correct if
necessary.
The output was incorrectly connected.
Check and correct the connection if
necessary.
"EEE" on the display
See error messages.
No connection to the device.
Incorrect device address
Correct the device address.
Different bus speeds (baud rate)
Correct the speed (baud rate).
Despite the aforementioned measures the
device does not work.
Device is defective.
Send the device to the manufacturer
for inspection and include a detailed
description of the error.
Содержание UMG 96 RM-M
Страница 13: ...13 UMG 96RM M...
Страница 15: ...15 UMG 96RM M...
Страница 33: ...33 UMG 96RM M...
Страница 65: ...65 UMG 96RM M Work values within the software GridVis Control of the values 187E 6270 10 resolution 62700 Wh...
Страница 81: ...81 UMG 96RM M...
Страница 102: ...102 UMG 96RM M Dimensional drawings All dimensions in mm max 6 91 5 104 96 42 Rear view Side view...
Страница 103: ...103 UMG 96RM M Bottom view 97 91 5 Cutout dimensions 92 0 8 92 0 8...
Страница 111: ...111 UMG 96RM M...