69
UMG 96RM-M
Pulse length (addr. 106)
The pulse length applies for both pulse outputs and is
permanently fixed via parameter address 106.
Adjustment range: 1 .. 1000 1 = 10ms
Default:
5
= 50ms
The typical pulse length for S0 pulses is 30 ms.
Pulse pause
The pulse pause is at least as long as the selected pulse
length.
The pulse pause depends on the measured energy,
for example, and can be hours or days.
Pulse length
10 ms .. 10 s
Pulse pause
>10 ms
Due to the minimum pulse length and minimum pulse
pause, the values in the table are for the maximum
number of pulses per hour.
Examples for the maximum possible number of pulses
per hour.
Pulse length
Pulse pause
Maximum pulses/hour
10 ms
10 ms
180,000 pulses/hour
30 ms
30 ms
60,000 pulses/hour
50 ms
50 ms
36,000 pulses/hour
100 ms
100 ms
18,000 pulses/hour
500 ms
500 ms
3,600 pulses/hour
1 s
1 s
1,800 pulses/hour
10 s
10 s
180 pulses/hour
Pulse spacing
The pulse spacing is proportional to the
power within the selected setting.