14
UMG 96RM-M
Installation
Supply voltage
A supply voltage is required to operate the UMG
96RM-M. The voltage supply is connected via plug-in
terminals on the back of the device.
Before applying the supply voltage, ensure that
the voltage and frequency correspond with the details
on the nameplate!
Fig. Connection example of the supply voltage
to the UMG 96RM-M
Separator
Fuse
N
L
m
• The supply voltage must be connected
through a fuse according to the techni-
cal data.
• In building installations, the supply voltage
must be provided with a disconnect switch
or circuit breaker.
• The disconnect switch must be attached
near the device and must be easily acces-
sible by the user.
• The switch must be labelled as a separator
for this device.
• Voltages that exceed the permissible vol-
tage range can destroy the device.