Comparator
Two comparator groups, each with
3 comparators, are available for
monitoring limit values. The results
from comparators A, B and C can
be AND or OR linked.
The linkage result from comparator
group 1 can be assigned to digital
output 1 and the linkage result from
comparator group 2 is assigned
to digital output 2.
The function “display blinking” can
be additionally assigned to every
comparator group. The effect is
the change of the display backlight
between maximum and minimum
brightness when the comparator
output is active (adr. 145).
Measured value (addr. 110)
Limit value (addr. 108)
Minimum turn-on time (addr. 111)
Lead time (addr. 112)
Operator ">=", "<" (addr. 113)
Comparator A
Measured value (addr. 116)
Limit value (addr. 114)
Minimum turn-on time (addr. 117)
Lead time (addr. 118)
Operator ">=", "<" (addr. 119)
Comparator B
Measured value (addr. 122)
Limit value (addr. 120)
Minimum turn-on time (addr. 123)
Lead time (addr. 124)
Operator ">=", "<" (addr. 125)
Comparator C
Comparator result (addr. 610)
Comparator result (addr. 611)
Comparator result (addr. 612)
Total running time
(addr. 5898)
Total running time
(addr. 5900)
Total running time
(addr. 5902)
Link the results from comparators A, B and C
Link the results from comparators A, B and C as AND or OR (addr. 107).
Comparator group 1
Linkage result (addr. 616)
Содержание UMG 96 RM-M
Страница 13: ...13 UMG 96RM M...
Страница 15: ...15 UMG 96RM M...
Страница 33: ...33 UMG 96RM M...
Страница 65: ...65 UMG 96RM M Work values within the software GridVis Control of the values 187E 6270 10 resolution 62700 Wh...
Страница 81: ...81 UMG 96RM M...
Страница 102: ...102 UMG 96RM M Dimensional drawings All dimensions in mm max 6 91 5 104 96 42 Rear view Side view...
Страница 103: ...103 UMG 96RM M Bottom view 97 91 5 Cutout dimensions 92 0 8 92 0 8...
Страница 111: ...111 UMG 96RM M...