89
UMG 96RM-M
Connection capacity of the terminals (power supply)
Connectable conductor. Only one conductor may be connected per contact point!
Single-wire, multi-wire, finely stranded conductor
0.2 - 2.5mm
2
, AWG 26 - 12
Pin terminals, ferrules
0.2 - 2.5mm
2
Tightening torque
0.4 - 0.5Nm
Stripping length
7mm
Power supply voltage
Option 230V
Nominal range
90V - 277V (50/60Hz) or DC 90V - 250V; 300V CATIII
Power consumption
max. 4.5VA / 2W
Option 24V
Nominal range
24V - 90V AC / DC; 150V CATIII
Power consumption
max. 2.5VA / 2W
Operating range
+-10% of nominal range
Internal fuse, not replaceable
Typ T1A / 250V/277V according IEC 60127
Recommended overcurrent protection device for line protection
(certified under UL)
Option 230V: 6 - 16A
Option 24V: 1 - 6A
(Char. B)
Recommendation for a maximum number of devices on a circuit breaker:
Option 230V : Circuit breaker B6A: max. 4 devices / Circuit breaker B16A: max. 12 devices
Option 24V : Circuit breaker B6A: max. 12 devices / Circuit breaker B16A: max. 35 devices