92
UMG 96RM-M
Current measurement
Rated current
5A
Metering range
0 .. 6Arms
Crest factor
1.98
Resolution
0.1 mA (display 0.01 A)
Overvoltage category
300V CAT II
Rated surge voltage
2kV
Power consumption
ca. 0.2 VA (Ri=5mOhm)
Overload for 1 sec.
120 A (sinusoidal)
Sampling rate
21.33 kHz (50 Hz), 25.6 kHz (60 Hz) per measuring channel
Connection capacity of the terminals (voltage and current measurement)
Connectable conductor. Only one conductor may be connected per contact point!
Current
Voltage
Single-wire, multi-wire, finely stranded conductor
0.2 - 2.5mm
2
, AWG 26-12
0.08 - 4.0mm
2
, AWG 28-12
Pin terminals, ferrules
0.2 - 2.5mm
2
0.2 - 2.5mm
2
Tightening torque
0.4 - 0.5Nm
0.4 - 0.5Nm
Stripping length
7mm
7mm
Содержание UMG 96 RM-M
Страница 13: ...13 UMG 96RM M...
Страница 15: ...15 UMG 96RM M...
Страница 33: ...33 UMG 96RM M...
Страница 65: ...65 UMG 96RM M Work values within the software GridVis Control of the values 187E 6270 10 resolution 62700 Wh...
Страница 81: ...81 UMG 96RM M...
Страница 102: ...102 UMG 96RM M Dimensional drawings All dimensions in mm max 6 91 5 104 96 42 Rear view Side view...
Страница 103: ...103 UMG 96RM M Bottom view 97 91 5 Cutout dimensions 92 0 8 92 0 8...
Страница 111: ...111 UMG 96RM M...