UMG 96RM-M
Mean value
Mean values are formed over an adjustable period
for the current, voltage and power measured values.
The mean values are identified with a bar above
the measured value.
The averaging time can be selected from a list of nine
fixed averaging times.
Current averaging time (addr. 040)
Power averaging time (addr. 041)
Voltage averaging time (addr. 042)
Setting
Baud rate
0
300 Baud
1
600 Baud
2
1200 Baud
3
2400 Baud
4
4800 Baud
5
9600 Baud
6
19200 Baud
7
38400 Baud
Baud rate (addr. 001)
A common baud rate is adjustable for the M-Bus inter-
faces. The baud rate must be chosen to be a uniform
value in the network. The parameter data bits (8), parity
(even) and stop bits (1) are permanently set.
Setting
Averaging time/sec.
0
5
1
10
2
15
3
30
4
60
5
300
6
480 (factory setting)
7
600
8
900
m
Note for setting the baud rate:
The baud rate is set directly on the device.
It is
not possible to set the baud rate via
M-Bus !