64
Range
- 0....65535 [engineering units]
Default
value
- 0 [engineering units]
Comments
- Sets
A Hi
flag used for rules processing. The reset level for this
flag depends on Alarm hysteresis value.
8.2.6.2.1.2.2.8. Alarm Lo
Function
- Defines
Lo
alarm level in engineering units for analogue input
signal.
Data type
- number
Range
- 0....65535 [engineering units]
Default
value
- 0 [engineering units]
Comments
- Sets
An Lo
flag used for rules processing. The reset level for
this flag depends on Alarm hysteresis value.
8.2.6.2.1.2.2.9. Alarm LoLo
Function
- Defines
LoLo
alarm level in engineering units for analogue
input signal.
Data type
- number
Range
- 0....65535 [engineering units]
Default
value
- 0 [engineering units]
Comments
- Sets
An Lo
flag used for rules processing. The reset level for
this flag depends on Alarm hysteresis value.
8.2.6.2.1.2.2.10. Alarm hysteresis
Function
- Defines hysteresis for analogue input alarm thresholds. The
value is in engineering units.
Data type
- number
Range
- 1....65535 [engineering units]
Default
value
- 10 [engineering units]
Comments
- setting proper hysteresis value for variable signal source
prevents frequent activation of alarm flag when signal source
is unstable.
8.2.6.2.1.2.2.11. Dead band
Function
- Defines size of dead band for value of analogue input in
engineering units.
Data type
- number
Range
- 0....65534 [engineering units]
Default
value
- 10 [engineering units]
Comments
- Insensitivity band spans symmetrically with last recorded
value in center. Upon crossing this value, the new value is
recorded and insensitivity band is moved. The
An DB
flag in
Содержание MT-101