75
Range
- 0....8640000 [s]
Default
value
- 0 [s]
Comments
-
0
(
zero
) value switches the clock off
8.2.6.5. Synchronous clocks
Synchronous clocks
group contains parameters set for two clocks capable of
cooperating with module real time (RTC) clock thus enabling triggering of events
synchronized with defined time.
8.2.6.5.1. Clock TMR3, TMR4
8.2.6.5.1.1. Start
Function
- synchronizes timer's clock setting start point and counting
period.
Data type
- time [HH:mm]
Range
- 0:00 - 23:59
Default
value
- 0:00
Comments
- n/a
8.2.6.5.1.2. Period
Function
- defines
synchronous clock
counting period in minutes.
Data type
- number
Range
-
0...1440 [min]
Default
value
-
0 [min]
Comments
-
0
(
zero
) value switches the clock off
8.2.6.6. Logger
This section's parameters define operation of internal
Logger
, recording state changes
on binary inputs/outputs and analogue inputs state. The capacity of internal buffer is 140
records. New records are written into memory after changes of state on binary
inputs/outputs or at crossing of dead band for analogue inputs.
8.2.6.6.1. Active
Function
- defines Logger status
Data type
- selection list
Range
-
Yes
Logger active
No
logger inactive
Default
value
-
No
Comments
- During MT-101 module operation, the state of Logger may be
remotely altered by
MLOG_act
bit in binary outputs space.
1
–
active,
0
– inactive.
Upon start of the logger, the first record of actual state is
created. Switching the Logger off triggers transmission of