44
8.2.3.15. Proxy server IP address
Function
- inserts Proxy server IP for selected
Proxy
Data frame format.
Data type
- IP address field
Range
- 0.0.0.0 - 255.255.255.255
Default value
- 0.0.0.0
Comments
- inserted IP is public static address of communication server
serving modules working in GSM/GPRS network with dynamic IP
assignment.
8.2.3.16. CRC compatibility
Function
- This parameter sets CRC calculation for systems requiring full
Modbus RTU compatibility.
Data type
- selection list
Range
-
Yes
For compatibility of Modbus RTU Slave mode, Modbus RTU
Master mode and Modbus RTU Mirror mode with remaining
modes, enabling the creation of systems consisting of
modules working in transparent modes and Modbus RTU
modes. This mode ensures compatibility with MT-DP
communication software .
No
for maintaining compatibility when expanding existent
systems operating in MODBUS modes or cooperating with
old versions of OPC driver.
Default value
-
Yes
Comments
- in new systems, it is recommended to leave the option at
default value
Yes
8.2.4. Authorized numbers
This group holds lists of telephone numbers and IP addresses authorized to communicate
with the Module.
Lists form the basis for assignment of privileges for configuring, receiving data and
sending commands.
Numbers on lists are the only ones allowed to be used for Rules processing.
8.2.4.1. Number of phone numbers
Function
- Defines length of phone number list that will receive SMS
messages. Each phone number has defined privileges for SMS
querying.
Data type
- number
Range
- 0....32
Default value
- 1
Comments
- The range value defines required volume of phone numbers
used in SMS Rules processing. See more in Phone