70
8.2.6.2.2.2.3.2. Counting range
Function
- defines max. value assumed by the counter
Data type
- number
Range
- 0....2 147 483 647 (31 bits + counting direction bit )
Default
value
- 0
Comments
- when counting up, the counter is zeroed by next appearing
pulse upon reaching declared value. When counting down,
next pulse writes declared value into the counter upon
reaching 0.
0
(
zero
) value switches counting off.
8.2.6.2.2.2.3.3. Activating slope
Function
- selects counting direction
Data type
- selection list
Range
-
Raising
The change of counter state occurs upon signal change
from 0 --> 1
Falling
The change of counter state occurs upon signal change
from 1 --> 0
Default
value
-
Raising
Comments
- n/a
8.2.6.2.2.2.3.4. Filtering constant
Function
- Defines (in seconds) value of min. duration of altered state on
input in order to consider state to be stable.
Data type
- number
Range
- 0,00....163,83 [s]
Default
value
- 0,00 [s]
Comments
- Setting value appropriate to contact characteristics eliminates
disturbance caused by contact bounce thus preventing multiple
registration of what is in reality one pulse.
8.2.6.2.2.2.4. Binary outputs
Binary outputs do not require any configuration.
8.2.6.2.3. Analogue inputs AN1, AN2
MT-101 Module is equipped with two identical Analogue inputs operating in 4-20mA
standard.
8.2.6.2.3.1. Name
Function
- allows setting a friendly name for the input usually connected
with performed function. Assigned name appears on the
terminals list
Data type
- text