71
Range
- letters and numerals, max. 16 characters
Default
value
- Resource Name (A1, A2)
Comments
- entering a friendly name facilitates distinguishing destination,
performed function and required settings.
8.2.6.2.3.2. Operating mode
Function
- defines analogue inputs operating mode
Data type
- selection list
Range
-
Analogue input
the input operates as 4-20 mA standard input
Default
value
-
Analogue input
Comments
- Parameter preserved for legacy support, not important for
operating analogue inputs A1, A2
8.2.6.2.3.3. Engineering units
Function
- Defines a name for engineering units for measured values.
Data type
- text
Range
- letters and numerals, max 16 characters
Default
value
- x
Comments
- inserted text does not have any influence on the value of
measured analogue signal
8.2.6.2.3.4. Low reference - internal units
Function
- used along with other reference parameters for rescaling input
signal range to engineering units range.
Data type
- number
Range
- 0....65535
Default
value
- 0
Comments
- low reference point for internal units
8.2.6.2.3.5. Low reference - engineering units
Function
- used along with other reference parameters for rescaling input
signal range to engineering units range.
Data type
- number
Range
- 0....65535
Default
value
- 400
Comments
- low reference point for engineering units
8.2.6.2.3.6. High reference - internal units
Function
- used along with other reference parameters for rescaling input
signal range to engineering units range.
Data type
- number