72
Range
- 1....65535
Default
value
- 65535
Comments
- high reference point for internal units
8.2.6.2.3.7. High reference - engineering units
Function
- used along with other reference parameters for rescaling input
signal range to engineering units range.
Data type
- number
Range
- 1....65535
Default
value
- 2000
Comments
- high reference point for engineering units
8.2.6.2.3.8. Alarm HiHi
Function
- Defines
HiHi
alarm level in engineering units for analogue
input signal.
Data type
- number
Range
- 0....65535 [engineering units]
Default
value
- 0 [engineering units]
Comments
- Sets
An HiHi
flag used for rules processing. The reset level for
this flag depends on Alarm hysteresis value.
8.2.6.2.3.9. Alarm Hi
Function
- Defines
Hi
alarm level in engineering units for analogue input
signal.
Data type
- number
Range
- 0....65535 [engineering units]
Default
value
- 0 [engineering units]
Comments
- Sets
An Hi
flag used for rules processing. The reset level for
this flag depends on Alarm hysteresis value.
8.2.6.2.3.9.1. Alarm Lo
Function
- Defines
Lo
alarm level in engineering units for analogue input
signal.
Data type
- number
Range
- 0....65535 [engineering units]
Default
value
- 0 [engineering units]
Comments
- Sets
An Lo
flag used for rules processing. The reset level for
this flag depends on Alarm hysteresis value.
8.2.6.2.3.10. Alarm LoLo
Function
- Defines
LoLo
alarm level in engineering units for analogue
input signal.
Data type
- number
Содержание MT-101