62
Default
value
-
Binary input
Comments
- selecting appropriate operating mode is the basis for taking full
advantage of module capabilities. It has an influence on
available configuration parameters optimizing module
performance.
8.2.6.2.1.2.1. Binary input
8.2.6.2.1.2.1.1. Filtering constant
Function
- Defines (in seconds) value of min. duration of altered state on
input in order to consider state to be stable.
Data type
- number
Range
- 0,00....163 [s]
Default
value
- 0,00 [s]
Comments
- Setting value appropriate to contact characteristics eliminates
disturbance caused by contact bounce thus preventing multiple
registration of what is in reality one pulse.
8.2.6.2.1.2.2. Analogue inputs
Function
- Defines time of measuring frequency of input signal in order to
convert it to analogue value.
Data type
- number
Range
- 0....255 [x 0,1 s]
Default
value
- 0
Comments
- for
0
(
zero
) value filtering is off.
Setting high time value influences stabilizing of result after
signal value change, but allows better precision of measuring
noisy signal.
8.2.6.2.1.2.2.1. Engineering units
Function
- Defines name for engineering units
Data
type
- text
Range
- letters and numerals, max 16 characters
Default
value
- x
Commen
ts
- inserted text does not have any influence on the value of
measured analogue signal
8.2.6.2.1.2.2.2. Low reference - internal units
Function
- used along with other reference parameters for rescaling input
signal range to engineering units range.
Data type
- number
Range
- 0....65535