65
binary inputs space is raised and may be used for rules
processing.
8.2.6.2.1.2.3. Counter inputs
8.2.6.2.1.2.3.1. Counting direction
Function
- defines counting direction
Data type
- selection list
Range
-
Up
A pulse on input increases value of counter register
Down
A pulse on input decreases value of counter register
Default
value
-
Up
Comments
- The counting process is valid only within range of Counting
range parameter.
8.2.6.2.1.2.3.2. Counting range
Function
- defines max. value assumed by the counter
Data type
- number
Range
- 0....2 147 483 647 (31 bits + counting direction bit )
Default
value
- 0
Comments
- when counting up the counter is zeroed by next appearing
pulse upon reaching declared value. When counting down,
next pulse writes declared value into the counter upon
reaching 0.
0
(
zero
) value switches counting off.
8.2.6.2.1.2.3.3. Activating slope
Function
- selects counting direction
Data type
- selection list
Range
-
Raising
The change of counter state occurs upon signal change
from 0 --> 1
Falling
The change of counter state occurs upon signal change
from 1 --> 0
Default
value
-
Raising
Comments
- n/a
8.2.6.2.1.2.3.4. Filtering constant
Function
- Defines (in seconds) value of min. duration of altered state on
input in order to consider state to be stable.
Data type
- number
Range
- 0,00....163,83 [s]
Default
value
- 0,00 [s]