76
logger content to defined recipient but only when it holds
records with data.
8.2.6.6.2. Sampling interval
Function
- Defines (in seconds) the interval of checking module inputs
state
Data type
- number
Range
- 0....1500 [s]
Default
value
- 0 [s]
Comments
-
0
(
zero
) value results in sampling interval of 100ms
8.2.6.6.3. Buffer flush mode
Function
- defines Logger buffer flush mode
Data type
- selection list
Range
-
Auto
Data collected in Logger are sent automatically upon filling
the buffer up or after Buffer flush interval time. The logger
is zeroed after transmission.
Upon request
Flushing Logger buffer is possible only by forcing
Default
value
-
Auto
Comments
- Flushing of Logger buffer may be remotely forced by setting
MLOG_rd bit
to
1
(one) in binary outputs space. Note that
when forcing, some data may get lost if querying is too slow
compared to object's dynamics. If the buffer gets filled
between readings, new data will replace oldest data so the
latest 140 records are preserved.
8.2.6.6.4. Buffer flush interval
Function
- Defines (in seconds) the interval of buffer flushing in automatic
mode
Data type
- number
Range
- 0....65535 [s]
Default
value
- 0 [s]
Comments
-
0
(
zero
) disables timed flushing. In any case, the Logger is
emptied upon buffer filling. Note that in timed flushing, frames
are sent only when buffer has at least 1 record.
8.2.6.6.5. Recipient IP address
Function
- defines IP address of device to send Logger buffer to.
Data type
- selection list
Range
- friendly names of IP of devices declared as Authorized to
communicate with module
Default
value
- IP1 - first number on the list of authorized numbers
Содержание MT-101