139
User has access to following triggering inputs:
input Description
I1...I8
binary inputs I1...I8
Q1...Q8
binary inputs/outputs Q1...Q8
A1, A2
Analogue inputs A1, A2
FS1_ups
= 1, no voltage on UPS pin
FS1_q+
= 1, no supply for binary outputs Q1...Q8
FS1_gprs
= 1, information of logging out of GPRS network
P1...P32
Program flags P1...P32 (definable in user program)
TMR1...TMR4
flags from Asynchronous clocks TMR1,TMR2 and synchronous
TMR3, TMR4
13.9. Flags
During operation
MT-101
module governs a number of binary flags (assuming value
True
or
False
) that trigger rules processing and remote diagnostics.
The User has access to following flags:
Flag resource
s
attached
Description
Bi In 0->1
Binary inputs
I1...I8,
Q1...Q8
Flag assuming value
True
after change of binary input from
0 to 1
Bi In 1->0
Binary inputs
I1...I8,
Q1...Q8
Flag assuming value
True
after change of binary input from
1 to 0
Bi In Chg
Binary inputs
I1...I8,
Q1...Q8
Flag assuming value
True
after any change of binary input
Bi Out Err
Binary
outputs.
Q1....Q8
Flag assuming value
True
if read outputs state does not
comply with set state
Counter
Binary inputs
I1...I8,
Q1...Q8
Flag assuming value
True
when counter reaches set value
or zero value (depending on counting direction)
An LoLo
Analogue
inputs
I1...I8
Q1...Q8
A1, A2
Flag assuming value
True
if value of analogue input is lower
than value set as Alarm LoLo(preserving relation to
hysteresis)
An Lo
Analogue
inputs
I1...I8
Q1...Q8
A1, A2
Flag assuming value
True
if value of analogue input is lower
than value set as Alarm Lo(preserving relation to
hysteresis)
An Hi
Analogue
inputs
I1...I8
Q1...Q8
A1, A2
Flag assuming value
True
if value if value of analogue input
is higher than value set as Alarm Hi(preserving relation to
hysteresis)