-105-
4 Keypad Display and Operations
■
Monitoring the DO level status through H0B-05
If the logic of all the three DO terminals are active at low level, the DO1 is high level and DO2 to DO5
terminals are low level, and the corresponding binary number is "001". In this case, the value of H0B-05
(Monitored DO signal) read by the software tool is 1 (decimal). The keypad display is as follows.
DO3
DO1
DO2
High
1
Low
0
Low
0
Figure 4-13 Display of H0B-05 when all DOs are "low level valid"
If the logic of all the three DOs are active at high level, the DO1 terminal is low level and DO2 to DO5
terminals are high level, the corresponding binary number is "110", and the value of H0B-05 (Monitored
DO signal) read by the software tool is 6 (decimal). The keypad display is as follows.
DO3 DO1
DO2
Low
0
High
1
High
1
Figure 4-14 Display of H0B-05 when all DOs are "high level valid"
■
Exit
The forced DO function is not retentive upon power-off. Normal DOs apply after restart, or you can set
H0D-17 (Forced DI/DO selection) to 0 (No operation) to return to the normal DO mode.
3 Forced DO signals controlled by the bus
After this function is enabled, all DO signal levels are controlled by 60FE-01h (Physical output).
In cases where the servo motor is used for vertical motion, if the brake output signal (FunOUT.9: BK,
brake output) is active, the brake will be released and the load may fall. Therefore, take protective
measures on the machine to prevent falling.
Содержание SV660
Страница 178: ...177 6 Gain Tuning Figure 6 18 Example of the waveform...
Страница 359: ...358 10 Application Cases c Click OK d Click Yes...
Страница 360: ...359 10 Application Cases e Click OK f Click No...
Страница 362: ...361 10 Application Cases...
Страница 366: ...365 10 Application Cases 7 2 Controlling the servo operations through the PLC a Create a PLC program...
Страница 370: ...369 10 Application Cases b Add parameters to be monitored to monitor these parameters during PLC running...