-104-
4 Keypad Display and Operations
■
Operating process
Start
Set the DO
function and logic
according to
group H04.
Set H0D-17 to 2 or
3 to enable forced
DO function.
Set H0D-19 to
activate or
deactivate the DO
function.
Monitor the DO
terminal level
status through
H0B-05.
End
Figure 4-11 Procedures for forced DO signal setting
H0D-19 (Forced DO value) is used to set whether the forced DO function is valid. The keypad displays the
value in hexadecimal, after being converted to binary, the number "1" indicates the DO function is valid
and "0" indicates the DO function is invalid.
Parameters in group H04 are used to set the DO logic. H0B-05 is used to monitor the DO level status. The
keypad displays the level, and the value of H0B-05 (Monitored DO signal) read by the software tool is a
decimal number.
Example: To activate the DO function allocated to DO1 and deactivate DO functions allocated to DO2 and
DO5, set as follows:
As the number "1" indicates the DO function is valid and "0" indicates the DO function is invalid, the
binary value will be "110", which corresponds to the hexadecimal number "6". Therefore, set H0D-19
(Forced DO value) to 6 through the keypad.
SET
0
DO1
1
DO3
1
DO2
Function
Figure 4-12
Description of H0D-19 setting
Содержание SV660
Страница 178: ...177 6 Gain Tuning Figure 6 18 Example of the waveform...
Страница 359: ...358 10 Application Cases c Click OK d Click Yes...
Страница 360: ...359 10 Application Cases e Click OK f Click No...
Страница 362: ...361 10 Application Cases...
Страница 366: ...365 10 Application Cases 7 2 Controlling the servo operations through the PLC a Create a PLC program...
Страница 370: ...369 10 Application Cases b Add parameters to be monitored to monitor these parameters during PLC running...