ABK2027IQE01_A - Installation and Operation Manual
•
Rule 21, Section Hh. (Revision through August 2nd, 2017) for California.
•
SRD-UL-1741-SA-V1.1 Updated: 9/26/2017 (Rule 14H) for Hawaii.
2.20.2. Utility – Interactive mode functions
This mode has the functions typically required by UL1741 before supplement A. They are basically voltage and
frequency protections, anti-islanding protection and DC current injection control:
•
High/low voltage protection.
•
High/low frequency protection.
•
Anti-islanding protection.
2.20.3. Grid Support Utility – Interactive mode functions
This mode includes the same functions as the Utility - Interactive mode except the low voltage protection
(incompatible with LVRT).
Additionally, it includes the following functions:
•
L/HVRT LOW AND HIGH VOLTAGE RIDE-THROUGH (SA9)
•
L/HFRT LOW AND HIGH FREQUENCY RIDE-THROUGH (SA10)
•
NORMAL RAMP RATE AND SS – SOFT-START RAMP RATE (SA11)
•
SPECIFIED POWER FACTOR (SA12)
•
VOLT/VAR MODE (Q(V)) (SA13)
•
FREQUENCY-WATT (FW) (SA14 OPTIONAL)
•
VOLT-WATT (VW) (SA15 OPTIONAL)
•
RATINGS FOR GRID SUPPORT UTILITY INTERACTIVE INVERTERS, CONVERTERS (SA16)
2.20.4. Ratings for grid support functions
In order to maintain a stable grid voltage, the inverters must be able to supply or absorb reactive power from/to
the EPS. One way to achieve this is to make the inverter supply or absorb reactive power in response to the EPS
voltage fluctuations.
The inverter's Volt-VAr mode implements the reactive power response to the EPS voltage fluctuations. This mode
works with the following parameters:
Test
Parameters
Acronym
Description
Units
Defined value
L/HVRT
td
Is dwell time (s) between pulses as specified by
manufacturer
s
5
MSA
Vac
AC voltage measurement accuracy
%V
1
MSA
t
Accuracy of time
s
0.0166
L/HFRT
td
Dwell time between pulses as specified by
manufacturer
s
5
MSA
Hz
Manufacturer’s stated AC frequency measurement
accuracy
Hz
0.1
MSA
t
Accuracy of time
s
0.01667
RR
I
rated
Output Current Rating
A
1500 @ 1500 Vdc
1600 @ 1000 Vdc
RR
norm_up_min
Minimum normal ramp-up rate
%I
rated
/sec
1
RR
norm_up_max
Maximum normal ramp-up rate
%I
rated
/sec
100
I
low
Minimum output current
A
15
MSA
RR
Ramp Rate Accuracy
%I
rated
/sec
2
td
Is dwell time between test iterations as specified by the
manufacturer
s
1
38
Unit description
Ingeteam
Содержание INGECON SUN 1000TL U B360
Страница 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Страница 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Страница 176: ...Notes...
Страница 177: ...Notes...
Страница 178: ...Notes...
Страница 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...