background image

I-7540D-MTCP Ethernet/ Modbus to CAN Converter Quick Start User Guide Version 1.0 ------ 1 

Quick Start User Guide 

 

1. Introduction 

 

This  manual  introduces  the  user  to  the  methods  used  to  implement  the 

I-7540D-MTCP  module  into  their  applications  in  a  quick  and  easy  way.  This 

will  only  provide  with  the  basic  instructions.  For  more  detailed  information, 

please  refer  to  the  I-7540D-MTCP  user  manual  located  on  the  ICPDAS 

CD-ROM or download it from the ICPDAS web site:   

Fieldbus_CD:\CAN\Converter\I-7540D-MTCP\ 

or 

http://www.icpdas.com/products/Remote_IO/can_bus/I-7540-MTCP.htm 

 

The goal of this manual is focused on helping users to quickly familiarize 

themselves  with  the  I-7540D-MTCP  module  and  the  CAN-Modbus  TCP 

/Modbus  RTU  communication  converter.  Here,  we  use  two  I-7540D-MTCP 

modules  (called  the  I-7540D-MTCP_A  and  the  I-7540D-MTCP_B)  as  the 

example  will  demonstrate  how  to  use  the  I-7540D-MTCP  modules.  The 

architecture of this example is depicted below. 

 

When the I-7540D-MTCP receives a valid Modbus TCP command, it can 

convert  this  command  into  a  CAN  message  and  transmits  it  into  the  CAN 

network.  Another  I-7540D-MTCP  will  receive  the  CAN message  then  store  it 

into  the  buffer.  Meanwhile,  user  can  use  Modbus  RTU  command  to  get  the 

message back.

I-7540D-MTCP   

Ethernet/Modbus TCP/Modbus RTU to CAN Converter

 

Содержание I-7540D-MTCP

Страница 1: ...I 7540 MTCP htm The goal of this manual is focused on helping users to quickly familiarize themselves with the I 7540D MTCP module and the CAN Modbus TCP Modbus RTU communication converter Here we use two I 7540D MTCP modules called the I 7540D MTCP_A and the I 7540D MTCP_B as the example will demonstrate how to use the I 7540D MTCP modules The architecture of this example is depicted below When t...

Страница 2: ... Set up the 120Ω terminator resistor of module A and B Before going to the next step check if the JP3 is enabled or not If not it is necessary to open the cover for each I 7540D MTCP and re configure their JP3 jumpers to enable them again as shown in below figure Enable default Activate Step2 Power connection for the I 7540D MTCP A and I 7540D MTCP B Connect the R Vs and B GND pins of the I 7540D ...

Страница 3: ...A 0910 The wire connection is shown below Step5 CAN bus connection Connect the CAN ports of these two I 7540D MTCP modules to the CAN network by using the following structure 3 The I 7540D MTCP Parameters Configuration Before testing the I 7540D MTCP converter users need to configure the RS 232 Ethernet and CAN parameters via the I 7540D MTCP Utility tool The details of this procedure are shown be...

Страница 4: ... I 7540D MTCP Utility The I 7540D MTCP Utility tool is located in the Fieldbus_CD can converter I 7540 MTCP utility folder on the companion CD ROM or can be downloaded from the web site http www icpdas com products Remote_IO can_bus I 7540d MTCP htm Step3 Click the Connect button to connect with the I 7540D MTCP A and the I 7540D MTCP B These steps are shown in the following figure Step4 Click the...

Страница 5: ... 0 5 Step5 After connecting with the I 7540D MTCP A you can modify the operation mode to Modbus TCP In the same way you can set the operation mode of I 7540D MTCP B to Modbus RTU The CAN parameters and network status of I 7540D MTCP A and I 7540D MTCP B are set as following table ...

Страница 6: ...8 0 1 IP 192 168 255 2 Mask 255 255 0 0 Gateway 192 168 0 1 4 Testing the I 7540D MTCP by using the I 7540D MTCP Utility Step1 Run the I 7540D MTCP Utility I 7540D MTCP exe two times Then two I 7540D MTCP Utility windows will be displayed on the screen Assume that one is named as Utility A and the other is called Utility B Step2 Click the Connect button to open the connection dialog Key in the IP ...

Страница 7: ...ssages to the ASCII command string and send it out through the PC s Ethernet port Suppose using Modbus function code 10 hex to send CAN message After the I 7540D MTCP A receives this command It will transfer the command to the CAN message So the I 7540D MTCP B will receive the CAN message transmitted from I 7540D MTCP A and store in the buffer User can use Modbus RTU command function code 04 hex t...

Страница 8: ...I 7540D MTCP Ethernet Modbus to CAN Converter Quick Start User Guide Version 1 0 8 Utility I 7540D MTCP B ...

Отзывы: