background image

I-7540D-MTCP Ethernet/ Modbus to CAN Converter Quick Start User Guide Version 1.0 ------ 6 

 

 

I-7540D-MTCP #A 

I-7540D-MTCP #B 

CAN parameters 

 

Specification: 2.0A 

CAN baud rate: 1M bps 

ACC: 00 00 00 00 

ACM: FF FF FF FF 

Err Response: No 

Time-stamp Response: No 

Specification: 2.0A 

CAN baud rate: 1M bps 

ACC: 00 00 00 00 

ACM: FF FF FF FF 

Err Response: No 

Time-stamp Response: No 

Network status   

 

IP: 192.168.255.1 

Mask: 255.255.0.0 

Gateway: 192.168.0.1 

IP: 192.168.255.2 

Mask: 255.255.0.0 

Gateway: 192.168.0.1 

 

4. Testing the I-7540D-MTCP by using the I-7540D-MTCP Utility 

 

Step1:    Run the I-7540D-MTCP Utility (I-7540D-MTCP.exe) two times. Then 

two  I-7540D-MTCP  Utility  windows  will  be  displayed  on  the  screen. 

Assume that one is named as Utility #A and the other is called Utility 

#B.   

 

Step2:   

Click the “Connect” button to open the connection dialog. Key-in the 

IP  of  these  I-7540D-MTCP

s  and  press  the  “Connect”  button  to 

connect with them.   

Step3:    After connecting with them, select the 

“Modbus Test” tab. Utility #A is 

shown in the below figure and Utility #B will be similar to Utility #A. 

 

Содержание I-7540D-MTCP

Страница 1: ...I 7540 MTCP htm The goal of this manual is focused on helping users to quickly familiarize themselves with the I 7540D MTCP module and the CAN Modbus TCP Modbus RTU communication converter Here we use two I 7540D MTCP modules called the I 7540D MTCP_A and the I 7540D MTCP_B as the example will demonstrate how to use the I 7540D MTCP modules The architecture of this example is depicted below When t...

Страница 2: ... Set up the 120Ω terminator resistor of module A and B Before going to the next step check if the JP3 is enabled or not If not it is necessary to open the cover for each I 7540D MTCP and re configure their JP3 jumpers to enable them again as shown in below figure Enable default Activate Step2 Power connection for the I 7540D MTCP A and I 7540D MTCP B Connect the R Vs and B GND pins of the I 7540D ...

Страница 3: ...A 0910 The wire connection is shown below Step5 CAN bus connection Connect the CAN ports of these two I 7540D MTCP modules to the CAN network by using the following structure 3 The I 7540D MTCP Parameters Configuration Before testing the I 7540D MTCP converter users need to configure the RS 232 Ethernet and CAN parameters via the I 7540D MTCP Utility tool The details of this procedure are shown be...

Страница 4: ... I 7540D MTCP Utility The I 7540D MTCP Utility tool is located in the Fieldbus_CD can converter I 7540 MTCP utility folder on the companion CD ROM or can be downloaded from the web site http www icpdas com products Remote_IO can_bus I 7540d MTCP htm Step3 Click the Connect button to connect with the I 7540D MTCP A and the I 7540D MTCP B These steps are shown in the following figure Step4 Click the...

Страница 5: ... 0 5 Step5 After connecting with the I 7540D MTCP A you can modify the operation mode to Modbus TCP In the same way you can set the operation mode of I 7540D MTCP B to Modbus RTU The CAN parameters and network status of I 7540D MTCP A and I 7540D MTCP B are set as following table ...

Страница 6: ...8 0 1 IP 192 168 255 2 Mask 255 255 0 0 Gateway 192 168 0 1 4 Testing the I 7540D MTCP by using the I 7540D MTCP Utility Step1 Run the I 7540D MTCP Utility I 7540D MTCP exe two times Then two I 7540D MTCP Utility windows will be displayed on the screen Assume that one is named as Utility A and the other is called Utility B Step2 Click the Connect button to open the connection dialog Key in the IP ...

Страница 7: ...ssages to the ASCII command string and send it out through the PC s Ethernet port Suppose using Modbus function code 10 hex to send CAN message After the I 7540D MTCP A receives this command It will transfer the command to the CAN message So the I 7540D MTCP B will receive the CAN message transmitted from I 7540D MTCP A and store in the buffer User can use Modbus RTU command function code 04 hex t...

Страница 8: ...I 7540D MTCP Ethernet Modbus to CAN Converter Quick Start User Guide Version 1 0 8 Utility I 7540D MTCP B ...

Отзывы: