2.12. Dimensions
110.9 in (2816 mm)
89.3 in (2268 mm)
40.83 in (1037 mm)
32.4 in (823 mm)
2.13. Characteristics of the electrical installation
These units are designed for connection to a dedicated grid with an IT-type neutral connection scheme. The IT
system neutral connection as a reference point is recommended.
An IT scheme has no directly grounded feed point.
In this system, the resulting intensity of a first phase against mass or phase against ground fault is sufficiently low
as to not cause the appearance of dangerous contact voltages.
The PV array must be installed, insulated from the earth in a configuration called
floating
to assure protection
against direct and indirect contacts. If requiring grounding for any part of the installation´s DC circuit, the
equipment must be equipped with the
PV array grounding kit
. If selecting this kit, see the installation and
operation manual.