ABK2027IQE01_A - Installation and Operation Manual
Medium height busbars for direct connection to transformer busbars
The AC phase busbars are located on the left or right side, depending on the unit configuration.
R
T
S
The connection is made directly to the transformer busbars.
The dimensions of the inverter busbars are as follows:
a
a
b
g
c
d
e
f
a
0.39 in (10 mm)
e
0.59 in (15 mm)
b
1.57 in (40 mm)
f
1.75 in (44.5 mm)
c
0.59 in (15 mm)
g
4.84 in (123 mm)
d
1.75 in (44.5 mm)
Connection for lower cable input
CAUTION
After connecting the cables to the inverter, ensure that the current distribution through the parallel conductors
is correct.
108
AC connection