ABK2027IQE01_A - Installation and Operation Manual
•
gPV class.
•
Rated current of 50 A
~
630 A, depending on the specifications of the unit.
Fuses of the following sizes and formats are allowed:
Number of inputs
Number of fuses
Fuse holder base size
Maximum size
Recommended size
with I
max
5
5 or 10
(1)
3L
630 A
630 A
6
6 or 12
(1)
3L
630 A
600 A
7
7 or 14
(1)
3L
630 A
500 A
8
8 or 16
(1)
3L
630 A
400 A
9
9 or 18
(1)
3L
630 A
350 A
10
10 or 20
(1)
3L
630 A
315 A
11
11 or 22
(1)
3L
630 A
315 A
12
12 or 14
(1)
3L
630 A
315 A
13
13 or 26
(1)
2XL
400 A
250 A
14
14 or 28
(1)
2XL
400 A
250 A
15
15 or 30
(1)
2XL
400 A
250 A
(1)
depending on whether it is installed on the positive pole or both poles.
2XL Mechanical specifications
max. 5.12 in (130 mm)
max. 6.85 in (174 mm)
max. 5.28 in (134 mm)
max. 2.91 in (74 mm)
max. 2.4 in (61 mm)
max. 0.24 in (6 mm)
max. 8.07 in (205 mm)
51
Preparation for installing the unit
Ingeteam
Содержание INGECON SUN 1000TL U B360
Страница 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Страница 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Страница 176: ...Notes...
Страница 177: ...Notes...
Страница 178: ...Notes...
Страница 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...