ABK2027IQE01_A - Installation and Operation Manual
Alarm
Name
Variable
Code
LED Lighting
Description
CSS system or
voltage sag system
4
0x0800
Red
Fault in the CSS system.
Replace the CSS or inspect the wiring.
CAN
communications
4
0x1000
Red
Communication error between the CCU and the devices
connected through the CAN bus, which are:
•
Grounding card (optional)
•
Display
•
TMD string measurement card (optional)
•
Other inverters that include the same cards
Grounding
4
0x2000
Red
Error in the system's grounding card.
Check the correct insulation of the PV array.
Inverter
communication
4
0x2000
Red
If the inverter is configured to stop if it loses
communication with the PPC, after a period without
frames the unit will stop by reducing its power ramp. The
unit starts normally once the communication is restored.
Warnings
The warnings are events that do not lead to the shut-down of the inverter but do need maintenance action.
Warnings
Name
Variable
Code
LED Lighting
Description
Blocked fan
1
0x0001
Orange
The fan could be blocked.
High temperature
1
0x0002
Orange
Power regulation via internal temperature of the inverter
greater than the operating temperature
Low temperature
1
0x0004
Orange
Power regulation via internal temperature of the inverter
lower than the operating temperature
DC overvoltage
1
0x0008
Orange
High DC input voltage
LVRT system
1
0x0080
Orange
Fault in the INGECON SUN LVRT electronic system
Insulation
1
0x0100
Orange
Insulation resistance out of range
LVRT system
1
0x0080
Orange
Fault in the INGECON SUN LVRT electronic system
Insulation
1
0x0100
Orange
Insulation resistance out of range
Low DC voltage
1
0x0200
Orange
Low voltage in the DC input.
Standby due to
power consumption
1
0x0400
Orange
Standby due to stoppage due to power consumption
CAN
communication
1
0x0800
Orange
Communication fault in the unit peripherals in the CAN
bus
Inverter
configuration
1
0x4000
Orange
The default configuration has been loaded in the inverter
High temperature
between phases
1
0x8000
Orange
The temperature difference between phases is above
10 ºC
Reasons for shutdown
Log file that indicates the alarms that have triggered the inverter shutdown, indicating the date and time of the
shutdown.
Reset stop reasons
This option resets the
Stop reasons
log file.
19.6.3. Start/Stop
The operation of the inverter can be stopped and started manually using this option.
136
Display control
Ingeteam
Содержание INGECON SUN 1000TL U B360
Страница 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Страница 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Страница 176: ...Notes...
Страница 177: ...Notes...
Страница 178: ...Notes...
Страница 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...