ABK2027IQE01_A - Installation and Operation Manual
6.4. Fixing surface area
The unit's excessive weight requires a firm base for support, completely horizontal and leveled, assuring proper
water drainage and avoiding water accumulation.
To perform the installation calculations it is necessary to take into account the loads that affect the environment
conditions, according to the country's regulations.
The following figures only show the vertical loads on each of the supports. The minimum number of supports is six,
as well as two additional optional ones. They differ depending on whether the inverter has the bottom cover kit:
Without bottom cover
2189 N
4363 N
3225 N
1930 N
4025 N
3010 N
107.82 in (2,739 mm)
i
i
i
39.29 in (998 mm)
33.11 in (841 mm)
43.58 in (1,107 mm)
26.69 in (678 mm)
31.22 in (793 mm)
i = 11.81 in (300 mm)
Footings
Area sealed for DC supply
Compulsory support points
Optional support points
Top view
46
Preparation for installing the unit
Ingeteam