SmartPLC DataLine with EtherNet/IP device interface
93
3 Set the number of analogue channels per output slave
►
Set the following parameter as required:
Parameter
Description
Possible values
[Analog. channels/O-slave] Number of analogue
channels transmitted per
output slave
[1 channel per A/B]
1 channel per A/B slave
OR:
channels 1 + 3 per single slave
[1 channel]
1 channel per single slave
OR:
1 channel per A slave
[2 channels]
2 channels per single slave
OR:
2 channels per A slave
[4 channels]
4 channels per single slave
OR:
2 channels per A/B slave
4 Set the failsafe state
►
Set the following parameter as required:
Parameter
Description
Possible values
[Failsafe state]
Behaviour of the slave
outputs in case of an
interrupted EtherNet/IP
connection
[Hold outputs]
The outputs hold the values which were
present immediately before the connection
was interrupted.
[Output reset]
The outputs are reset to their initial values.
5 Set the byte order of a word
►
Set the following parameter as required:
Parameter
Description
Possible values
[Change byte order]
Byte order in a data word
Byte order remains unchanged.
Byte order is inverted.
6 Save the changes
►
Press [Accept] button.
>
Selected values are applied.