SmartPLC DataLine with EtherNet/IP device interface
143
>
Parameter setting via the configuration assembly object
Content
Device-specific parameters ..................................................................................................................144
Parameters of the fieldbus slots ...........................................................................................................153
Derivation of parameter values for free slave assignment .................................................................159
41804
In
→
Configuration mode: Top-Down
(
), the parameter data are set in the EtherNet/IP projection
software (
→
Configuration mode: Top-Down
(
)). By means of the configuration assembly object,
the configuration is then transferred to the device and activated.
Only when a connection is established by the I/O scanner will the parameter data configured
via the configuration assembly object be transferred to the device. Changes to the parameter
data in the online mode of the controller will therefore only become effective after the next
connection.
To trigger a new connection setup, perform one of the following actions:
Reboot the device
Perform a system reset (
→
System reset
(
Briefly interrupt the EtherNet/IP connection between the I/O scanner and the device
Transfer the project from the higher-level controller to the device (download)
Restart the I/O scanner
The configuration in top-down mode includes the following parameters:
Parameters of the fieldbus slots
(
Device-specific parameters
(